KEX, Regulation in the Rack Nr. WSLA 16.0.3
Place: in the Booster (ABOMA-KEX)
Supply: 30'000Volt / 20mA Knürr-Heinzinger 30'000-20 UMP Current: nominal 1200A max. 2300A
Current transformer 1 : Pearson model 411, number 9X'XXX.
1000A 100V (1M Ohm) 50V (50 Ohm) ,near the magnet.
Cable from current transformer 1 to regulation nr: 30'000-10733 Current transformer 2 : Pearson model 411, number 9X'XXX.
1000A 100V (1M Ohm) 50V (50 Ohm)
Cable from current transformer 2 to regulation nr: 30'000-10734 Attenuator : Input 50 Ohm 20dB 30Watt RADIALL R41720139, 3dB RADIALL R412703000 and 50 Ohm Attenuator
1000A1000/(10*10*2*1,4125)= 3.54Volt
Factors
Current measurementfactor CPD : 100A 0.383V.
Voltage supply measurement : 30kV 8.9V Vset : 10V 30kV
Bsp. Vset 6.8Volt 20'556Volt 1611A
Fail level
Limite for current 2390A (9.13Volt)
Limite for voltage supply 30'000V (9.8Volt)
LabViev factors Supply Faktor 3384 I read Faktor 261 I set Faktor 236.2
Measurement: 1600A. 20'462Volt